HUBBELL POWER SYSTEMS
Regulator By-Pass Switch, 14.4kV 150kV LIW 1200A Station Class

Regulator By-Pass Switch, 14.4kV 150kV LIW 1200A Station Class

Brand: Chance

14.4kV, 110kV LIW, 1200A Station Regulator By-Pass Switch.

  • Fully Compliant with ANSI/IEEE C37.30.1
  • For Station Class Regulator Bypass Applications
  • Designed for use with Regulators that can be set on Neutral
  • Single Pull Sequenced Operation
  • 15 & 27/38kV Voltage Classes
  • 150 & 200kV BIL Insulation Levels
  • 600A and 1200A Current Ratings
  • TR Rated Post Insulator to provide standoff for most substation requirements
  • Utilizes the Interrupter on our AR Automation Ready Gang Operated Switches
  • Station Base for Structure mounting

General

Blade Type

Solid Copper (two blade truss-member)

Color - Insulator

Dark Gray

Insulator Type

Polymer (2 1/4" Bolt Circle), 3" Bolt Circle Procelain

Material - Base

Galvanized Steel per ASTM A153

UPC

096359387930

Dimensions

Dimensions

30.250 in x 17.750 in x 22.375 in

Height

22.375 in

Length

30.25 in

Weight

90 lb

Width

17.75 in

Electrical Ratings

BIL

150 kV

Creep and Leakage Distance

28.2" (716.3mm)

Reference Voltage Limit - Minimum

14.4kV

Temperature Rise - Max. at 600A

33° C

Voltage - Maximum

15 kV

Withstand Current - Short Time (1 sec)

40kA, symmetrical (switch circuit)

Withstand Current - Short Time (10 cycles)

99kA peak (switch circuit)

Certifications And Compliance

Industry Standard(s)

All Applicable ANSI/IEEE Standards

Logistics

Standard Package

1