Gleason_DWR12-0751_ProdImage

SDC™ Composite Bushing - 8.7KV

Brand: Gleason Reel

SDC™ 8.7kV-1200A Transformer Condenser Bushing, Solid-Dielectric-Capacitor Type, Rated per IEEE C57.19.01, Bottom Connected for Air-to-Oil Applications, 7.4" Min.Oil Immersion Level/CT Pocket, 14.3" Min. Creepage Length

Electro Composites SDC™ composite bushings are designed to provide the toughest, cleanest and safest bushing solution for all HV applications. We make standard OEM and aftermarket form-fit-function replacement bushings for substation transformers, GSU transformers, oil circuit breakers, switchgear, wall/floor (air-air and oil-oil), HVDC and other applications. Available from 1kV up to 170kV with current ratings up to 21,500A. SDC™ (Solid Dielectric Capacitor) bushigs have a one-piece cycloaliphatic epoxycore and integral sheds. All SDC bushings are solid dielectric insulation – oil–free construction, capacitance graded condenser core with internal CT pocket/ground shield and a flange test tap, available in bottom connected or draw-lead configurations. Made in accordance with the most current bushing standards: IEEE C57.19.01, CSA C88.1, IEC 60137.

  • SDC™ - Solid Dielectric Capacitance Graded Composite Construction
  • EC-APG-02 Cycloaliphatic Epoxy Compound for Optimal Performance
  • No oil, paper or porcelain
  • Can be mounted vertically or horizontally
  • Meets IEEE C57.19.01 Electrical and Mechanical Requirements

For Bushing Test Terminals, please see here

General

Application

Transformer

Color

Gray

Material - Flange

Aluminum

Material - Insulation

APG-02 - Cycloaliphatic Epoxy

Plating - Bottom Terminal

None

Test Tap

Yes

Top Terminal Plating

None

Top Terminal Type

1 1/8-12

Type

SDC - Solid Dielectric Capacitor

Dimensions

Above Flange Length

11.94 in

Below Flange Length

16.06 in

Diameter - Above Flange Maximum

5.21 in

Diameter - Below Flange Maximum D <gt/> 1"

2.76 in

Diameter - Below Flange Maximum P

2.94 in

Diameter - Live Part Bottom

1.25 in

Diameter - Live Part Top

2.75 in

Effective Length - Bottom Terminal

2.30 in

Effective Length - Top Terminal

2.13 in

Flange Mounting Hole Bolt Circle

6.25 in

Flange Mounting Hole Diameter

0.63 in

Flange Outside Diameter

7.5 in

Length

28 in

Length - Drawlead Above Flange

NA

Length - Ground Shield

7.40 in

Length - Insulation Above Flange

5.70 in

Length - Insulation Below Flange

13.76 in

Length - Live Part Bottom

2.30 in

Length - Live Part Top

2.90 in

Length - Minimum Oil Immersion Level

7.40 in

Sealing Surface Inside Diameter

3.01 in

Sealing Surface Outside Diameter

5.62 in

Top Terminal Min. Thread Length

2.13 in

Weight

25 lb

Electrical Ratings

BIL

95 kV

Current Rating

1200 A

kV Class

8.7 kV

Minimum Creepage

14.3 in

Minimum Creepage - Inside

NA

Minimum Strike

6.9 in

Minimum Strike - Inside

NA

Withstand Voltage - 60 Hz Dry

35 kV

Certifications And Compliance

Industry Standard(s)

IEEE C57.19.01